Voltage Drop Calculator

Drop for a cable run, and the smallest size that passes. Metric units, change any unit beside its field.

Measurements

About this calculator

Voltage drop on a branch or sub-main cable for single- and three-phase supplies, plus the smallest conductor that keeps you within your limit.

How it’s calculated

VD = 2 × ρ × L × I ÷ A for single-phase, or √3 for three-phase. ρ ≈ 0.0225 Ω·mm²/m for copper at operating temperature, 0.036 for aluminium.

Worked example

With these inputs:

Supply
230 V single-phase
Load current (A)
30
One-way cable length
30 m
Conductor
Copper
Conductor size
6 mm²
Allowed drop (%)
5

the result is:

Voltage drop
6.75 V (2.93%)
Voltage at load
223.3 V
Smallest size for ≤5% drop
4 mm²

Tips from the trade

  • BS 7671 Appendix 4 typically allows 3% for lighting and 5% for other uses on a public supply.
  • Long runs to outbuildings and EV chargers are where voltage drop usually decides the cable size.

Results are estimates for planning and pricing. Check quantities against your drawings, the manufacturer’s data and the Building Regulations before ordering.